FLAT-FLEX® (PVC) Festooning Cable 600 VOLT UL & CSA 105°C TO -40°C

 

Extra-flexible stranding (Class M for 16 and 14AWG and Class K for 12 AWG and larger), soft-drawn uncoated copper; per ASTM B-3, ASTM B-172, UL-62 and CSA Electrical Bulletin 1447. Colour-coded, flame and oil-resistant 105°C PVC insulation per UL-62 (CSA FT-1 flame rated). Flat parallel conductor grouping, one rip cord per group, and webbing between groups. Available in stock with either Yellow or Black, flame and oil-resistant PVC jacket; UL VW-1 and CSA FT-1, FLAT-FLEX® Festooning Cables are UL Listed (E60362H) and CSA certified (File No. LL95915-1), 600 volts, 105°C to -40°C.

Applications

ECS
Catalogue
Number
Conductor AMPS* Insulation
(inches)
Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
Colour Code Chart
No. AWG
Size
Stranding
FF16-08 8 16 65 x 34 14 .030 .225 x 1.170 636 3
FF16-12 12 16 65 x 34 14 .030 .225 x 1.700 958 3
FF14-04 4 14 105 x 34 2 .030 .240 x 0.690 452 3
FF14-08 8 14 105 x 34 19 .030 .240 x 1.290 833 3
FF14-12 12 14 65 x 30 19 .030 .240 x 1.825 1,246 3
FF12-04 4 12 65 x 30 33 .030 .260 x 0.800 590 3
FF12-08 8 12 65 x 30 23 .030 .260 x 1.440 1,125 3
FF10-04 4 10 105 x 30 44 .030 .290 x 0.890 784 3
FF08-04 4 8 168 x 30 60 .045 .375 x 1.225 1,316 3
FF06-04 4 6 259 x 30 82 .060 .450 x 1.500 2,083 3
FF04-04 4 4 413 x 30 104 .060 .515 x 1.750 9,775 3
FF02-04 4 2 665 x 30 142 .060 .575 x 1.975 912 3
FF001-04 4 1/0 1045 x 30 186 .080 .750 x 2.600 7,287 3
FF002-04 4 2/0 1323 x 30 213 .080 .800 x 2.820 8,573 3
SHIELDED FLAT CABLE (Each Conductor has TC Braid Shield)
FFS16-04 4 16 65 x 30 20 .030 .250 x 0.800 532 3
FFS16-12 12 16 65 x 30 14 .030 .260 x 2.125 1,496 3
FFS14-12 12 14 105 x 30 19 .030 .270 x 2.200 1,709 3
FIVE CONDUCTOR FLAT CABLES (Exhibition Center Types)
FF12-05 5 12 65 x 30 23 .030 .260 x 0.990 754 4
FF10-05 5 10 105 x 30 31 .030 .290 x 1.150 1,083 4
FF06-05 5 6 259 x 30 57 .060 .450 x 1.920 2,624 4
FF04-05 5 4 413 x 30 73 .060 .525 x 2.200 3,904 4
FF02-05 5 2 665 x 30 99 .060 .570 x 2.530 5,728 4

 

*Ampacities (Amps per conductor) are based on 40°C ambient temperature in air per the 1999 NEC, Table 400-5(A). Ampacities for 3/C and 4/C cords assume 1 conductor is used as a ground or neutral and does not carry current. Ampacities for 5/C cords assume 2 conductors are used as ground and neutral and do not carry current.

 

Applications:

Primarily designed for use with festoon systems for carrying electrical power and control to cranes, hoists or any other equipment which travels with a lateral traversing motion. FLAT-FLEX cables can also be used where space is at a premium, since it can be stacked; FLAT-FLEX cables are widely used in convention halls and exhibit centers as under carpet cables for distribution and booth lighting. Flat cable has several advantages over round cable. The main benefit is one can usually use a smaller carrier than with same round cable since the minimum bend radius of flat cable can be 1/3 or less of the round. Since the bend radius is tighter and all the conductors are in one plane, flat cable will easily compress into a ribbon shape when in storage. Round cable has a tendency to twist and sometimes catch on other loops. The flat design also makes it easy to stack multiple cables into a compact package.